Power Line Filters MTK-F Series
Power Line Filters
-
5 to 200 Amps circuits.
-
600 VDC, 0-277 Vac Line to Neutral.
-
0-480 Vac Line to Line
-
0-60 Hz.
-
400 Hz. Filters available, contact MTK
FEATURES
-
Designed, manufactured and tested to the applicable portions of MIL-F-15733.
-
Each Individual filter circuit is replaceable in the field without the use of special tools.
-
Each individual filter is hermetically sealed.
-
Terminals: Each circuit is terminated with a flexible lead to an electrical standoff preventing damage to the terminals.
-
Maximum voltage drop: 2 Volts.
-
Maximum operating Temperature 85ºC.
-
Overload safety: 140% rated current for 15 minutes.
-
Case: Steel all welded construction suitably plated on groundng surfaces and painted or plated on all other surfaces.
* "G" Denotes that case includes grounded neutral conductor stud.
![](https://static.wixstatic.com/media/ef71d7_ae8db3dddc004fa9bb402b528721cf35~mv2.jpg/v1/fill/w_381,h_144,al_c,q_80,usm_0.66_1.00_0.01,enc_auto/ef71d7_ae8db3dddc004fa9bb402b528721cf35~mv2.jpg)
Insertion Loss: 100db from 14 KHz to 10 GHz measured in accordance with MIL-STD-220A, load condition. Also measured under full load condition from 14 KHz to 20 MHZ with extended range buffer networks.